[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [datacenter] AC settings



Datacenter temperature is open for speculation :) but I believe
that the Bellcore standard is < 71F. I don't have the docs
in front of me.

Now, I'm not saying that's what you should use, but I typically
take the Bellcore recommendation, and adapt it to my needs, wants,
and $$$.

Remember, every degree is going to cost you power. Also, did you get
humidifiers with your units? That's where people will complain i.e.
if it's too wet, or too dry.

-M



Regards,

--
Martin Hannigan			[email protected]
Boston, MA			http://www.fugawi.net

On Fri, 28 Jun 2002 [email protected] wrote:

> We have a new datacenter with dual split-system air conditioners
> installed. The first is set for 72f and the second for 74f as a backup.
> The ductwork blows air down over open racks (no raised floor or cabinets
> here). What do other people choose for temperatures in datacenters? I know
> from past experience that certain pieces of equipment (hard drives for
> example) become ever so slightly less reliable if they are run in 80+
> indoor temperature all the time.
>
> We caged off particular areas of the building for physical security
> instead of using cabinets. We got a great deal on 19" racks from a well
> known failed dotcommer datacenter here in New England.
>
> Also, some time ago, I asked questions about experiences with Cummins/Onan
> diesel generators and received good responses. I went ahead and had one
> installed. We've had a 35KW 3-phase Cummins/Onan diesel now for a while
> and are quite happy with it. We went with all the options like the coolant
> heater, auto transfer switch with excerciser and battery charger, external
> fuel tank, etc...
>
> Jason Philbrook
> Midcoast Internet Solutions
>
> ---------------------------------------------------------------------
> To unsubscribe, e-mail: [email protected]
> For additional commands, e-mail: [email protected]
>
>


---------------------------------------------------------------------
To unsubscribe, e-mail: [email protected]
For additional commands, e-mail: [email protected]